TY - JOUR AU - Kumara, Isnu Gita AU - Prasetyono, Rizki Noor PY - 2021/10/04 Y2 - 2024/03/28 TI - FEASIBILITY ANALYSIS OF GROUNDING RESISTANCE FROM THE ELECTRICITY DISTRIBUTION NETWORK AT PT. PLN (PERSERO) ULP: Array JF - Journal of Electronic and Electrical Power Applications JA - jeepa VL - 1 IS - 2 SE - Articles DO - UR - https://journal.peradaban.ac.id/index.php/jeepa/article/view/846 SP - 15-21 AB - <p style="text-align: justify;">The grounding system is direct protection against instrumentality and human. The grounding process is carried out using the principle of creating a path for the fault current to the ground and making the equipment have a potential that is close to the value of the ground potential. The supply of a grounding system should be supported by the grounding resistance worth needed by PUIL, which is below 5 Ohm. To maintain the value of grounding resistance, it is necessary to check each 6 months in step with the standards of PUIL. The grounding test was carried out using an earth tester. In the analysis of the 7 grounding points of the PT. PLN (Persero) ULP Bumiayu concluded that there are 4 grounding points that have met PUIL standards because the value of their grounding resistance is below 5 Ohm.&nbsp; Meanwhile, the other 3 points haven't met PUIL standards because they are worth more than 5 Ohm</p> ER -